Negative air machines for asbestos abatement

INLINE Distributing sells HEPA negative air machines for asbestos removal from Abatement Technologies, Aerospace America, ACSI, Dri-Eaz, Novatek, OmniTec, Phoenix and XPOWER, plus its own INLINE 2000 and INLINE 700. Top rated airflow runs from 500 CFM on compact units to 2,000 CFM on machines with 10 or 12 in exhaust. INLINE also sells replacement HEPA filters, ring panels, pre-filters, poly duct and manometers online, by quote, or through the order desk at 1-800-795-0933.

Negative air calculatorSolicitar cotizaciónDepartamento de pedidos 1-800-795-0933Find a branch

INLINE 2000 negative air machine on a concrete floor
INLINE 2000 negative air machine

At a glance

  • Top rated airflow runs from 500 CFM on the Phoenix Guardian R to 2,000 CFM on the Abatement Technologies 2000, Bulldog and Novatek Novair 2000.
  • CFM needed equals containment volume in cubic feet times air changes per hour, divided by 60.
  • Exhaust sizes: 12 in on Abatement Technologies and Aeroclean units, 10 in on the Novatek Novair 2000, 14 in duct on the Dri-Eaz HEPA 700.
  • The Novatek Novair 2000 lists 2,000 CFM with filters in place and takes a standard 24 x 24 x 11.5 in HEPA filter.
  • The INLINE 2000 is 26 in wide, runs 1,900 CFM high and 1,200 low, and the INLINE 2000A adds a differential pressure gauge and audible alarm.
  • Order online, paste part numbers on the Quick Order page, send a job list through the quote form, or call 1-800-795-0933.

Compare negative air machines side by side

Each row lists the maker, rated airflow, filter stages, power draw, weight and exhaust size exactly as the product page gives them, so you can match a machine to the containment, the doorway and the circuit before you order. Where a figure reads Not listed, the order desk can look it up. Replacement filters, ring panels, parts and duct follow the table.

MachineAirflowFiltraciónPowerPesoDuct
Abatement TechnologiesAbatement Technologies 2000Airflow2,000 CFM high, 1,200 CFM lowFiltración99.97% HEPA, 6 in. deep (also takes a 12 in. HEPA)PowerNot listedPesoNot listedDuct12 in. exhaust collar
Abatement TechnologiesAbatement Technologies BulldogAirflow2,000 CFM high, 1,200 CFM lowFiltración99.97% HEPA, 6 in. deep (also takes a 12 in. HEPA)PowerNot listedPesoNot listedDuct12 in. exhaust collar
NovatekNovatek Novair 2000Airflow2,000 CFM high, 1,000 CFM lowFiltraciónHEPA, 24 x 24 x 11.5 in.Power115 V, 15 APeso135 lbDuct10 in. exhaust port
ACSIACSI Force Air 2000ECAirflowAbout 2,000 CFM high, 1,000 CFM lowFiltraciónThree-stage: pre-filter, ring panel, 99.97% HEPAPower115 V, 20 APeso140 lbDuctNot listed
Aerospace AmericaAeroclean 2000 EconoAirflow1,950 CFM high, 1,300 CFM lowFiltraciónNot listedPower1 HP motorPeso135 lb shipping weightDuct12 in. exhaust
INLINEINLINE 2000Airflow1,900 CFM high, 1,200 CFM lowFiltraciónPolypad pre-filter, pleated pre-filter, 99.97% HEPAPower1 HP motorPesoNot listedDuctNot listed
Aerospace AmericaAeroclean Mighty Mite 1800Airflow1,850 CFM high, 1,200 CFM lowFiltraciónThree-stage: pre-filter, ring panel, HEPAPower115 V, 9.4 APeso94 lbDuct12 in. exhaust
OmniTecOmniAire 2000VAirflow300 to 1,600 CFM, variableFiltraciónPrimary and secondary filters, 99.97% HEPAPowerNot listedPeso110 lbDuctNot listed
INLINEINLINE 700Airflow400 to 700 CFM, variableFiltraciónPre-filter, pleated pre-filter, 99.97% HEPAPowerNot listedPesoNot listedDuctNot listed
ACSIACSI FA700Airflow400 to 700 CFM, adjustableFiltraciónPrimary and secondary filters, 99.97% HEPAPower115 V, 3.3 APesoNot listedDuctNot listed
Dri-EazDri-Eaz HEPA 700Also in blackAirflow275 to 700 CFM, variableFiltración2 in. pre-filter, HEPAPower115 V, 3.0 APeso42 lbDuct14 in. duct
XPOWERXPOWER X-2480AAirflowUp to 550 CFM, 5 speedsFiltración3-stage: mesh pre-filter, pleated filter, 99.97% HEPAPower115 V, 2.8 APeso23.6 lbDuct6 in. outlet
PhoenixPhoenix Guardian RAirflow250 to 500 CFM, variableFiltración2-stage: pleated pre-filter, 99.97% HEPAPower110 to 120 V, 2.4 APeso33 lbDuct16 in. inlet

Figures as each maker lists them on the product page. Airflow drops as filters load and with long or bent duct.

Negative air machines for asbestos removal by size class

INLINE Distributing sells negative air machines in five working classes. A 140 lb ACSI Force Air 2000EC is the wrong tool for a 640 cu ft bathroom, and a 23.6 lb XPOWER X-2480A will not carry a school wing. Pick the class from the air changes your project specification calls for, then the machine by exhaust size, amp draw and doorway width on the air scrubbers and negative air machines shelf.

Negative air machine classes INLINE sells
ClassMachinesRated airflowWhere it fits
Class2,000 CFMMachinesAbatement Technologies 2000 and Bulldog, Novatek Novair 2000, ACSI Force Air 2000ECRated airflow2,000 high, 1,000 to 1,200 lowWhere it fitsFloors, school wings, commercial gut-outs
Class1,850 to 1,950 CFMMachinesINLINE 2000, Aeroclean Mighty Mite 1800, Aeroclean 2000 EconoRated airflow1,900, 1,850, 1,950 highWhere it fitsSame jobs; Mighty Mite is 18 in wide for tight halls
ClassVariable mid-sizeMachinesOmniAire 2000V, 110 lbRated airflow300 to 1,600Where it fitsOne unit that throttles to the room; positive or negative
Class700 CFMMachinesINLINE 700, ACSI FA700, Dri-Eaz HEPA 700Rated airflow400 to 700; Dri-Eaz 275 to 700Where it fitsSingle rooms, bathrooms, stackable fleets
ClassCompactMachinesPhoenix Guardian R, 33 lb; XPOWER X-2480A, 23.6 lbRated airflow250 to 500; up to 550Where it fitsMini-containments, crawlspaces, small work areas

Negative air machine vs air scrubber: what changes when you add duct

Often it is the same HEPA box. Ducted through the barrier to outdoors, it pulls air out of the enclosure faster than air leaks in, so every leak runs inward. Three things change once duct goes on. Delivered airflow drops, because the duct adds resistance. The exhaust joint has to seal, so you need a collar or lipped outlet you can clamp and tape. And placement matters: the machine sits at the far end from the decon entry so air sweeps across the work toward the filters.

The Phoenix Guardian R has a 16 in inlet and a detachable outlet duct ring for lay-flat duct, and the XPOWER X-2480A a lipped 6 in outlet. The OmniAire 2000V can hold positive or negative pressure, and with optional intake manifold adapters it sits outside the containment and pulls through flexible hose.

CFM and air changes per hour: sizing math for a containment

CFM needed equals containment volume in cubic feet times the air changes per hour, divided by 60. Many abatement specifications set a floor of 4 air changes an hour and some ask for 6 or more; your project specification sets the number. Measure height to the deck, not the drop ceiling, when tiles come out, because the plenum is part of the volume. Then divide by the airflow each unit really delivers, round up, and add the backup unit if the job's requirements call for one. To check an existing setup, run it backward: ACH equals total delivered CFM times 60, divided by volume.

Worked sizing, counting each 2,000 CFM unit at 1,400 CFM delivered
ContainmentVolumeCFM at 4 ACHCFM at 6 ACH2,000 CFM units at 4 / 6 ACH
ContainmentBathroom 8 x 10 x 8 ftVolume640 cu ftCFM at 4 ACH43CFM at 6 ACH642,000 CFM units at 4 / 6 ACHUse a 700 CFM unit on low
ContainmentClassroom 30 x 30 x 10 ftVolume9,000 cu ftCFM at 4 ACH600CFM at 6 ACH9002,000 CFM units at 4 / 6 ACH1 / 1
ContainmentOffice floor 50 x 60 x 9 ftVolume27,000 cu ftCFM at 4 ACH1,800CFM at 6 ACH2,7002,000 CFM units at 4 / 6 ACH2 / 2
ContainmentSchool wing 100 x 60 x 10 ftVolume60,000 cu ftCFM at 4 ACH4,000CFM at 6 ACH6,0002,000 CFM units at 4 / 6 ACH3 / 5
ContainmentGym 80 x 100 x 22 ftVolume176,000 cu ftCFM at 4 ACH11,733CFM at 6 ACH17,6002,000 CFM units at 4 / 6 ACH9 / 13
Sizing calculator

How many negative air machines does your containment need

Enter the containment size, the air changes your project specification calls for and the machine you plan to run. The starting example is a 50 x 60 x 9 ft office floor at 4 air changes per hour with one backup unit.

Contención

When ceiling tiles come out, measure to the deck: the plenum is part of the volume.

Cambios de aire por hora

Many abatement specifications set a floor of 4 air changes an hour and some ask for 6 or more; your project specification sets the number.

70 percent is the planning figure for a loaded HEPA plus a short duct run, about 1,400 CFM on a 2,000 CFM unit. It is a planning allowance, not test data.

Máquinas
3
2 working plus 1 backup
Volumen
27,000
cubic feet
Required airflow
1,800
CFM at 4 air changes per hour
Air changes achieved
5.9
per hour from the working units
Delivered per unit
1,330 CFM (1,900 rated x 70 percent)
Power
Amps not listed for this machine; the order desk can look them up.

How this is calculated: 50 x 60 x 9 = 27,000 cu ft. 27,000 x 4 / 60 = 1,800 CFM. 1,900 x 70 percent = 1,330 CFM per unit. 1,800 / 1,330 = 1.35, rounded up to 2. 2 x 1,330 x 60 / 27,000 = 5.9 air changes per hour.

The same job with other machines

Request a quote for these machines

This is a planning estimate from listed ratings. Your project specification governs the air changes, the pressure differential and the backup. Circuits are planned at 80 percent of the breaker rating, 12 A on a 15 A circuit. Check the manometer reading once the machines run.

Rated CFM vs delivered CFM on a 2,000 CFM negative air machine

The number on the label is airflow with clean filters and little or no duct. Only the Novatek Novair 2000 listing says its 2,000 CFM is with filters in place. Labels also differ by machine: the INLINE 2000 lists 1,900 CFM on high, the Aeroclean 2000 Econo 1,950 and the Mighty Mite 1800 1,850, and the OmniAire 2000V tops out at 1,600 despite its name. The allowances below are planning figures, not test data.

  • Loaded HEPA plus a short duct run: plan each 2,000 CFM unit at about 1,400 CFM, roughly 70 percent of the label.
  • Running on low: count the low rating, 1,200 CFM on the Abatement Technologies units and the INLINE 2000, 1,000 on the Novatek and ACSI 2000EC.
  • Exhaust runs past about 50 ft or with more than two bends: move the unit closer to the exhaust point or add a unit rather than stretch the duct.
  • Variable units: count the dial setting you will run, not the top of the range, on the OmniAire 2000V, INLINE 700, ACSI FA700 and Dri-Eaz HEPA 700.

Flex duct size and poly tubing for negative air exhaust

Match the duct to the collar and keep the run short, straight and taut; slack, kinked or crushed duct costs more airflow than length does. At 2,000 CFM, air moves about 2,550 ft per minute in 12 in duct, about 3,670 in 10 in duct and over 5,300 in 8.3 in duct. Resistance climbs steeply with speed, so keep 10 in runs on the Novatek short, and treat 8.3 in lay-flat as a compact-unit duct. At 700 CFM the same 8.3 in duct runs about 1,860 ft per minute.

6 mil clear poly tubing is 20 in wide flat, which opens to about 12.7 in round, enough to slide over a 12 in collar and clamp or tape. Dri-Eaz Layflat Ducting is 4 mil, 13 in wide flat, opens to 8.3 in and comes 500 ft to a roll to cut to length. For wire-reinforced flex duct in a set diameter, ask the order desk.

Exhaust size by machine
MachineExhaust or duct sizeDuct that fits
MachineAbatement Technologies 2000, BulldogExhaust or duct size12 in collar; 2000 also has a 12 in inlet manifoldDuct that fits12 in flex or 20 in poly tubing
MachineAeroclean Mighty Mite 1800, 2000 EconoExhaust or duct size12 in exhaustDuct that fits12 in flex or 20 in poly tubing
MachineNovatek Novair 2000Exhaust or duct size10 in exhaust portDuct that fits10 in flex, short runs
MachineDri-Eaz HEPA 700Exhaust or duct size14 in duct sizeDuct that fits14 in duct
MachinePhoenix Guardian RExhaust or duct sizeOutlet duct ring for lay-flat ductDuct that fitsLay-flat duct
MachineXPOWER X-2480AExhaust or duct size6 in lipped outletDuct that fits6 in duct

Makeup air, manometer readings and a containment that will not hold

Makeup air normally enters through the decon chambers and any filtered openings the specification allows, at the end opposite the machines, so clean air crosses the workers toward the HEPA units. Many abatement specifications set a minimum differential of 0.02 in. of water column, about 5 pascals, read on a manometer or recorder. The Dwyer Mark II 25 reads 0 to 3 in-WC at plus or minus 3 percent of full scale, fine for spot checks. The OmniGuard 6 logs the reading, lists accuracy of 0.003 in WC or 1 percent of reading, and sounds a 95 dB alarm at the high and low limits you set.

  • Reading drifts toward zero over the shift: change the pre-filter first, then the ring panel. If fresh filters do not restore it, the HEPA is loaded.
  • New setup never reaches target: look for open poly seams, floor and wall joints and penetrations, then recheck the CFM math.
  • Poly bellies inward and tape lifts: the room is over-negative. Drop a unit to low or turn down a variable unit, or open a filtered makeup vent at the far end.
  • Reading falls to zero at once: a breaker or GFCI tripped. Restart, start the backup unit, and recheck the circuit load.
Containment under negative pressure, plan viewA poly walled work area with a three chamber decon at the left end: clean room, shower and equipment room. Makeup air enters through the decon, sweeps across the work area and reaches two negative air machines at the right end, which exhaust through flex duct and the outside wall. A manometer reads across the barrier at the top, and a waste load-out leaves from the bottom wall.Outdoors
  1. 1. Work area: poly walls and floor, held under negative pressure
  2. 2. Clean room, the entry from outside the containment
  3. 3. Ducha
  4. 4. Equipment room, next to the work area
  5. 5. Makeup air enters through the decon chambers, at the end opposite the machines
  6. 6. Air sweeps across the work area toward the machines, so clean air crosses the workers toward the HEPA units
  7. 7. Negative air machines at the far end from the decon entry
  8. 8. Flex duct carries the exhaust through the wall to outdoors; clamp and tape each joint so it seals
  9. 9. Manometer or pressure recorder reading the difference across the barrier; your project specification sets the target
  10. 10. Waste load-out, where bagged waste leaves the work area

Schematic, not to scale. Chamber sizes, layers and the pressure target come from your project specification.

Plan view of a containment under negative pressure: air comes in through the decon and sweeps across the work area to the negative air machines at the far end.

Amps per negative air machine and how many share a circuit

Negative air runs around the clock, so plan circuits at 80 percent of the breaker rating, 12 A on a 15 A circuit. Put each large unit on its own circuit and spread the fleet across circuits, so one trip does not drop the whole containment. The daisy-chain outlets on the XPOWER X-2480A and the 15 A GFCI receptacle on the Phoenix Guardian R pass power along, but every unit on the chain still counts against the same breaker.

Feed large units with 12 gauge cord such as the Voltec 50 ft 12 gauge U-Ground cord or the U.S. Wire 25 ft 12 gauge cord. ACSI calls for a 12-3 cord no longer than 50 ft on the Force Air 2000EC, and the Aeroclean Mighty Mite 1800 ships without a power cord, so order one with it.

Listed amps and per-circuit planning at 115 V
MachineListed ampsPer 15 A circuit, 12 A continuous
MachineACSI Force Air 2000ECListed amps20 APer 15 A circuit, 12 A continuousOwn circuit; confirm nameplate amps
MachineNovatek Novair 2000Listed amps15 APer 15 A circuit, 12 A continuousOwn 20 A circuit
MachineAeroclean Mighty Mite 1800Listed amps9.4 APer 15 A circuit, 12 A continuous1
MachineACSI FA700Listed amps3.3 APer 15 A circuit, 12 A continuous3
MachineDri-Eaz HEPA 700Listed amps3.0 APer 15 A circuit, 12 A continuous4
MachineXPOWER X-2480AListed amps2.8 APer 15 A circuit, 12 A continuous4
MachinePhoenix Guardian RListed amps2.4 APer 15 A circuit, 12 A continuous5

Replacement HEPA filters and pre-filters by machine

Filters load in order: the pre-filter takes the bulk dust and often goes daily during heavy removal, the ring panel or pleated secondary goes when a fresh pre-filter no longer restores the reading, and the HEPA goes last, when the gauge, change lamp or alarm says so. Bag used filters inside the containment and handle them as asbestos waste under your project specification, using asbestos disposal bags.

INLINE's wood HEPA filters are all 11-1/2 in deep and rated 99.97 percent at 0.3 micron, in faces from 12 x 12 to 24 x 24 in. Ring panels come 24 to a case and primary pre-filters 50 to a case, both in 16 x 24 and 24 x 24 among other sizes.

Filter stages and sizes from each machine's listing
MachineStages listedReplacement match
MachineAeroclean Mighty Mite 1800Stages listed24 x 16 pre-filter, 24 x 16 x 1 ring panel, 24 x 16 x 11-7/8 HEPAReplacement match16 x 24 pre-filters and ring panels; the 16 x 24 wood HEPA is 3/8 in shallower
MachineNovatek Novair 2000Stages listed24 x 24 x 11.5 HEPA or nuisance dust filter, 1/2 in pad ringReplacement match24 x 24 x 11-1/2 wood HEPA, 24 x 24 pre-filters
MachineAbatement Technologies 2000, BulldogStages listed6 in deep 99.97 percent HEPA; accepts 12 in deepReplacement matchFace size by quote
MachineDri-Eaz HEPA 700Stages listed2 in MERV 8 pre-filter, primary HEPAReplacement matchDri-Eaz 125026 pre-filter, 125028 HEPA
MachinePhoenix Guardian RStages listed1 x 18 x 18 pleated, 2 x 18 x 18 HEPAReplacement matchBy quote
MachineINLINE 2000 and 700Stages listedPolypad or coarse prefilter, pleated prefilter, 99.97 percent tested HEPAReplacement matchBy quote

Products mentioned on this page

Questions contractors ask

Does a 2,000 CFM negative air machine really move 2,000 CFM with duct on it?

Usually not once the HEPA loads and duct is attached. The label is clean-filter airflow; only the Novatek Novair 2000 listing says its 2,000 CFM is with filters in place. Plan each 2,000 CFM unit at about 1,400 CFM and let the manometer confirm the containment holds.

What size poly tubing fits a 12 inch exhaust collar?

Poly tubing 20 in wide flat fits a 12 in collar. A 20 in flat width opens to about 12.7 in round, so it slides over the collar on the Abatement Technologies 2000, Bulldog and Aeroclean machines and can be clamped or taped. INLINE sells 6 mil clear poly tubing 20 in by 500 ft.

How many negative air machines can I plug into one 15 amp circuit?

Plan to 12 A of continuous load on a 15 A circuit and divide by each unit's listed amps: 5 Phoenix Guardian R units at 2.4 A, 4 XPOWER X-2480A or Dri-Eaz HEPA 700 units, 3 ACSI FA700 units, or 1 Aeroclean Mighty Mite 1800 at 9.4 A. The Novatek Novair 2000 (15 A) and ACSI Force Air 2000EC (20 A listed) each need their own circuit.

Can a negative air machine pull too much on a small containment?

Yes. A large unit on a small room can suck the poly inward and pull tape loose. A unit rated at 2,000 CFM moves about 187 air changes an hour in a 640 cu ft bathroom. Use a 700 CFM class unit on low, a variable unit such as the OmniAire 2000V turned down, or open a filtered makeup vent at the end away from the machine.

What should the manometer read on an asbestos containment?

Many abatement specifications set a minimum of 0.02 in. of water column below the surrounding area, about 5 pascals; your project specification sets the exact figure and how it is recorded. A reading that climbs while the poly bows in means the room is over-negative; one that drifts down means filters are loading or a seam has opened.

Do I need a backup negative air machine on an asbestos job?

Plan for one whenever the job's requirements call for it, and many do. Size the standby to at least match the largest running unit, so a filter change or breaker trip does not drop the containment, and put it on a separate circuit from the units it backs up.

Which negative air machine fits through a standard doorway?

The narrowest large unit is the Aeroclean Mighty Mite 1800 at 18 in wide and 94 lb. The INLINE 2000, Aeroclean 2000 Econo and Novatek Novair 2000 are 26 in wide, and the ACSI Force Air 2000EC lists 37-1/8 x 26.5 x 32.5 in. Smaller stackable units weigh far less: the Dri-Eaz HEPA 700 is 42 lb, the Phoenix Guardian R 33 lb and the XPOWER X-2480A 23.6 lb.

Will a 24 x 24 x 11-1/2 wood HEPA filter fit my negative air machine?

It matches the Novatek Novair 2000, which lists a standard 24 x 24 x 11.5 in HEPA. It does not match the Aeroclean Mighty Mite 1800, which uses a 24 x 16 x 11-7/8 in HEPA, or the Abatement Technologies units, which take a 6 in or 12 in deep HEPA. For other machines, send the make and model through the quote form before you order.