Negative air machines for asbestos abatement
INLINE Distributing sells HEPA negative air machines for asbestos removal from Abatement Technologies, Aerospace America, ACSI, Dri-Eaz, Novatek, OmniTec, Phoenix and XPOWER, plus its own INLINE 2000 and INLINE 700. Top rated airflow runs from 500 CFM on compact units to 2,000 CFM on machines with 10 or 12 in exhaust. INLINE also sells replacement HEPA filters, ring panels, pre-filters, poly duct and manometers online, by quote, or through the order desk at 1-800-795-0933.
Negative air calculatorSolicitar cotizaciónDepartamento de pedidos 1-800-795-0933Find a branch

At a glance
- Top rated airflow runs from 500 CFM on the Phoenix Guardian R to 2,000 CFM on the Abatement Technologies 2000, Bulldog and Novatek Novair 2000.
- CFM needed equals containment volume in cubic feet times air changes per hour, divided by 60.
- Exhaust sizes: 12 in on Abatement Technologies and Aeroclean units, 10 in on the Novatek Novair 2000, 14 in duct on the Dri-Eaz HEPA 700.
- The Novatek Novair 2000 lists 2,000 CFM with filters in place and takes a standard 24 x 24 x 11.5 in HEPA filter.
- The INLINE 2000 is 26 in wide, runs 1,900 CFM high and 1,200 low, and the INLINE 2000A adds a differential pressure gauge and audible alarm.
- Order online, paste part numbers on the Quick Order page, send a job list through the quote form, or call 1-800-795-0933.
Compare negative air machines side by side
Each row lists the maker, rated airflow, filter stages, power draw, weight and exhaust size exactly as the product page gives them, so you can match a machine to the containment, the doorway and the circuit before you order. Where a figure reads Not listed, the order desk can look it up. Replacement filters, ring panels, parts and duct follow the table.
| Machine | Airflow | Filtración | Power | Peso | Duct |
|---|---|---|---|---|---|
| Abatement TechnologiesAbatement Technologies 2000 | Airflow2,000 CFM high, 1,200 CFM low | Filtración99.97% HEPA, 6 in. deep (also takes a 12 in. HEPA) | PowerNot listed | PesoNot listed | Duct12 in. exhaust collar |
| Abatement TechnologiesAbatement Technologies Bulldog | Airflow2,000 CFM high, 1,200 CFM low | Filtración99.97% HEPA, 6 in. deep (also takes a 12 in. HEPA) | PowerNot listed | PesoNot listed | Duct12 in. exhaust collar |
| NovatekNovatek Novair 2000 | Airflow2,000 CFM high, 1,000 CFM low | FiltraciónHEPA, 24 x 24 x 11.5 in. | Power115 V, 15 A | Peso135 lb | Duct10 in. exhaust port |
| ACSIACSI Force Air 2000EC | AirflowAbout 2,000 CFM high, 1,000 CFM low | FiltraciónThree-stage: pre-filter, ring panel, 99.97% HEPA | Power115 V, 20 A | Peso140 lb | DuctNot listed |
| Aerospace AmericaAeroclean 2000 Econo | Airflow1,950 CFM high, 1,300 CFM low | FiltraciónNot listed | Power1 HP motor | Peso135 lb shipping weight | Duct12 in. exhaust |
| INLINEINLINE 2000 | Airflow1,900 CFM high, 1,200 CFM low | FiltraciónPolypad pre-filter, pleated pre-filter, 99.97% HEPA | Power1 HP motor | PesoNot listed | DuctNot listed |
| Aerospace AmericaAeroclean Mighty Mite 1800 | Airflow1,850 CFM high, 1,200 CFM low | FiltraciónThree-stage: pre-filter, ring panel, HEPA | Power115 V, 9.4 A | Peso94 lb | Duct12 in. exhaust |
| OmniTecOmniAire 2000V | Airflow300 to 1,600 CFM, variable | FiltraciónPrimary and secondary filters, 99.97% HEPA | PowerNot listed | Peso110 lb | DuctNot listed |
| INLINEINLINE 700 | Airflow400 to 700 CFM, variable | FiltraciónPre-filter, pleated pre-filter, 99.97% HEPA | PowerNot listed | PesoNot listed | DuctNot listed |
| ACSIACSI FA700 | Airflow400 to 700 CFM, adjustable | FiltraciónPrimary and secondary filters, 99.97% HEPA | Power115 V, 3.3 A | PesoNot listed | DuctNot listed |
| Dri-EazDri-Eaz HEPA 700Also in black | Airflow275 to 700 CFM, variable | Filtración2 in. pre-filter, HEPA | Power115 V, 3.0 A | Peso42 lb | Duct14 in. duct |
| XPOWERXPOWER X-2480A | AirflowUp to 550 CFM, 5 speeds | Filtración3-stage: mesh pre-filter, pleated filter, 99.97% HEPA | Power115 V, 2.8 A | Peso23.6 lb | Duct6 in. outlet |
| PhoenixPhoenix Guardian R | Airflow250 to 500 CFM, variable | Filtración2-stage: pleated pre-filter, 99.97% HEPA | Power110 to 120 V, 2.4 A | Peso33 lb | Duct16 in. inlet |
Figures as each maker lists them on the product page. Airflow drops as filters load and with long or bent duct.
Filters and ring panels
- Carbon Pre-Filter - 24” x 24” - 50/Case
- Carbon Ring Panel Filter
- Dri-Eaz 1st Stage Pre-Filters (HEPA 500 Air Scrubber)
- Dri-Eaz 2nd Stage Pre-Filters (HEPA 500 Air Scrubber)
- Dri-Eaz Activated Carbon Filter for HEPA 500
- Dri-Eaz F321 Replacement HEPA for Hepa 500 Air Scrubber - Negative Air Machine
- Dri-Eaz MERV 8 Pre-Filter for HEPA 700 Air Scrubber, 2 in
- Dri-Eaz Replacement HEPA Filter for DefendAir HEPA 700, 8/Case
- Omnitec OmniAire Nitro 600 HEPA Filter
- Pleated Air Filter 12/Case
- Pre-Filters (Primary)
- Ring Panels (Secondary) - 12” x 12” - 24/Case
- Ring Panels (Secondary) - 16” x 16” - 24/Case
- Ring Panels (Secondary) - 16” x 24” - 24/Case
- Ring Panels (Secondary) - 18” x 18” - 24/Case
- Ring Panels (Secondary) - 18” x 24” - 24/Case
- Ring Panels (Secondary) - 24” x 24” - 24/Case
- Wood Hepa Air Filter - 12” x 12” x 11-1/2"
- Wood Hepa Air Filter - 16” x 16” x 11-1/2"
- Wood Hepa Air Filter - 16” x 18” x 11-1/2"
- Wood Hepa Air Filter - 16” x 24” x 11-1/2"
- Wood Hepa Air Filter - 18” x 18” x 11-1/2"
- Wood Hepa Air Filter - 24” x 12” x 11-1/2"
- Wood HEPA Air Filter, 24" × 24" × 11-1/2"
Parts and duct
- 6 Mil Clear Poly Tubing, 20 in. x 500 ft
- Dri-Eaz Layflat Ducting
- Husqvarna 201000014 Pre-Filter, 12 x 12 x 1 in, for A1000 and A600 Air Scrubbers
- Husqvarna 590427701 HEPA Filter
- Husqvarna 590460801 HEPA Replacement Filter for A 600 Air Scrubber
- Husqvarna 590480801 Transport Cover, Protective Cover for A 600 Air Scrubber
Negative air machines for asbestos removal by size class
INLINE Distributing sells negative air machines in five working classes. A 140 lb ACSI Force Air 2000EC is the wrong tool for a 640 cu ft bathroom, and a 23.6 lb XPOWER X-2480A will not carry a school wing. Pick the class from the air changes your project specification calls for, then the machine by exhaust size, amp draw and doorway width on the air scrubbers and negative air machines shelf.
| Class | Machines | Rated airflow | Where it fits |
|---|---|---|---|
| Class2,000 CFM | MachinesAbatement Technologies 2000 and Bulldog, Novatek Novair 2000, ACSI Force Air 2000EC | Rated airflow2,000 high, 1,000 to 1,200 low | Where it fitsFloors, school wings, commercial gut-outs |
| Class1,850 to 1,950 CFM | MachinesINLINE 2000, Aeroclean Mighty Mite 1800, Aeroclean 2000 Econo | Rated airflow1,900, 1,850, 1,950 high | Where it fitsSame jobs; Mighty Mite is 18 in wide for tight halls |
| ClassVariable mid-size | MachinesOmniAire 2000V, 110 lb | Rated airflow300 to 1,600 | Where it fitsOne unit that throttles to the room; positive or negative |
| Class700 CFM | MachinesINLINE 700, ACSI FA700, Dri-Eaz HEPA 700 | Rated airflow400 to 700; Dri-Eaz 275 to 700 | Where it fitsSingle rooms, bathrooms, stackable fleets |
| ClassCompact | MachinesPhoenix Guardian R, 33 lb; XPOWER X-2480A, 23.6 lb | Rated airflow250 to 500; up to 550 | Where it fitsMini-containments, crawlspaces, small work areas |
Negative air machine vs air scrubber: what changes when you add duct
Often it is the same HEPA box. Ducted through the barrier to outdoors, it pulls air out of the enclosure faster than air leaks in, so every leak runs inward. Three things change once duct goes on. Delivered airflow drops, because the duct adds resistance. The exhaust joint has to seal, so you need a collar or lipped outlet you can clamp and tape. And placement matters: the machine sits at the far end from the decon entry so air sweeps across the work toward the filters.
The Phoenix Guardian R has a 16 in inlet and a detachable outlet duct ring for lay-flat duct, and the XPOWER X-2480A a lipped 6 in outlet. The OmniAire 2000V can hold positive or negative pressure, and with optional intake manifold adapters it sits outside the containment and pulls through flexible hose.
CFM and air changes per hour: sizing math for a containment
CFM needed equals containment volume in cubic feet times the air changes per hour, divided by 60. Many abatement specifications set a floor of 4 air changes an hour and some ask for 6 or more; your project specification sets the number. Measure height to the deck, not the drop ceiling, when tiles come out, because the plenum is part of the volume. Then divide by the airflow each unit really delivers, round up, and add the backup unit if the job's requirements call for one. To check an existing setup, run it backward: ACH equals total delivered CFM times 60, divided by volume.
| Containment | Volume | CFM at 4 ACH | CFM at 6 ACH | 2,000 CFM units at 4 / 6 ACH |
|---|---|---|---|---|
| ContainmentBathroom 8 x 10 x 8 ft | Volume640 cu ft | CFM at 4 ACH43 | CFM at 6 ACH64 | 2,000 CFM units at 4 / 6 ACHUse a 700 CFM unit on low |
| ContainmentClassroom 30 x 30 x 10 ft | Volume9,000 cu ft | CFM at 4 ACH600 | CFM at 6 ACH900 | 2,000 CFM units at 4 / 6 ACH1 / 1 |
| ContainmentOffice floor 50 x 60 x 9 ft | Volume27,000 cu ft | CFM at 4 ACH1,800 | CFM at 6 ACH2,700 | 2,000 CFM units at 4 / 6 ACH2 / 2 |
| ContainmentSchool wing 100 x 60 x 10 ft | Volume60,000 cu ft | CFM at 4 ACH4,000 | CFM at 6 ACH6,000 | 2,000 CFM units at 4 / 6 ACH3 / 5 |
| ContainmentGym 80 x 100 x 22 ft | Volume176,000 cu ft | CFM at 4 ACH11,733 | CFM at 6 ACH17,600 | 2,000 CFM units at 4 / 6 ACH9 / 13 |
How many negative air machines does your containment need
Enter the containment size, the air changes your project specification calls for and the machine you plan to run. The starting example is a 50 x 60 x 9 ft office floor at 4 air changes per hour with one backup unit.
- Delivered per unit
- 1,330 CFM (1,900 rated x 70 percent)
- Power
- Amps not listed for this machine; the order desk can look them up.
How this is calculated: 50 x 60 x 9 = 27,000 cu ft. 27,000 x 4 / 60 = 1,800 CFM. 1,900 x 70 percent = 1,330 CFM per unit. 1,800 / 1,330 = 1.35, rounded up to 2. 2 x 1,330 x 60 / 27,000 = 5.9 air changes per hour.
- Novatek Novair 2000, 2,000 CFM high2 plus 1 backup, 6.2 air changes per hour, 3 circuits
- Aeroclean Mighty Mite 1800, 1,850 CFM high2 plus 1 backup, 5.8 air changes per hour, 3 circuits
- Abatement Technologies 2000, 2,000 CFM high2 plus 1 backup, 6.2 air changes per hour
- Dri-Eaz HEPA 700, up to 700 CFM4 plus 1 backup, 4.4 air changes per hour, 2 circuits
Request a quote for these machines
This is a planning estimate from listed ratings. Your project specification governs the air changes, the pressure differential and the backup. Circuits are planned at 80 percent of the breaker rating, 12 A on a 15 A circuit. Check the manometer reading once the machines run.
Rated CFM vs delivered CFM on a 2,000 CFM negative air machine
The number on the label is airflow with clean filters and little or no duct. Only the Novatek Novair 2000 listing says its 2,000 CFM is with filters in place. Labels also differ by machine: the INLINE 2000 lists 1,900 CFM on high, the Aeroclean 2000 Econo 1,950 and the Mighty Mite 1800 1,850, and the OmniAire 2000V tops out at 1,600 despite its name. The allowances below are planning figures, not test data.
- Loaded HEPA plus a short duct run: plan each 2,000 CFM unit at about 1,400 CFM, roughly 70 percent of the label.
- Running on low: count the low rating, 1,200 CFM on the Abatement Technologies units and the INLINE 2000, 1,000 on the Novatek and ACSI 2000EC.
- Exhaust runs past about 50 ft or with more than two bends: move the unit closer to the exhaust point or add a unit rather than stretch the duct.
- Variable units: count the dial setting you will run, not the top of the range, on the OmniAire 2000V, INLINE 700, ACSI FA700 and Dri-Eaz HEPA 700.
Flex duct size and poly tubing for negative air exhaust
Match the duct to the collar and keep the run short, straight and taut; slack, kinked or crushed duct costs more airflow than length does. At 2,000 CFM, air moves about 2,550 ft per minute in 12 in duct, about 3,670 in 10 in duct and over 5,300 in 8.3 in duct. Resistance climbs steeply with speed, so keep 10 in runs on the Novatek short, and treat 8.3 in lay-flat as a compact-unit duct. At 700 CFM the same 8.3 in duct runs about 1,860 ft per minute.
6 mil clear poly tubing is 20 in wide flat, which opens to about 12.7 in round, enough to slide over a 12 in collar and clamp or tape. Dri-Eaz Layflat Ducting is 4 mil, 13 in wide flat, opens to 8.3 in and comes 500 ft to a roll to cut to length. For wire-reinforced flex duct in a set diameter, ask the order desk.
| Machine | Exhaust or duct size | Duct that fits |
|---|---|---|
| MachineAbatement Technologies 2000, Bulldog | Exhaust or duct size12 in collar; 2000 also has a 12 in inlet manifold | Duct that fits12 in flex or 20 in poly tubing |
| MachineAeroclean Mighty Mite 1800, 2000 Econo | Exhaust or duct size12 in exhaust | Duct that fits12 in flex or 20 in poly tubing |
| MachineNovatek Novair 2000 | Exhaust or duct size10 in exhaust port | Duct that fits10 in flex, short runs |
| MachineDri-Eaz HEPA 700 | Exhaust or duct size14 in duct size | Duct that fits14 in duct |
| MachinePhoenix Guardian R | Exhaust or duct sizeOutlet duct ring for lay-flat duct | Duct that fitsLay-flat duct |
| MachineXPOWER X-2480A | Exhaust or duct size6 in lipped outlet | Duct that fits6 in duct |
Makeup air, manometer readings and a containment that will not hold
Makeup air normally enters through the decon chambers and any filtered openings the specification allows, at the end opposite the machines, so clean air crosses the workers toward the HEPA units. Many abatement specifications set a minimum differential of 0.02 in. of water column, about 5 pascals, read on a manometer or recorder. The Dwyer Mark II 25 reads 0 to 3 in-WC at plus or minus 3 percent of full scale, fine for spot checks. The OmniGuard 6 logs the reading, lists accuracy of 0.003 in WC or 1 percent of reading, and sounds a 95 dB alarm at the high and low limits you set.
- Reading drifts toward zero over the shift: change the pre-filter first, then the ring panel. If fresh filters do not restore it, the HEPA is loaded.
- New setup never reaches target: look for open poly seams, floor and wall joints and penetrations, then recheck the CFM math.
- Poly bellies inward and tape lifts: the room is over-negative. Drop a unit to low or turn down a variable unit, or open a filtered makeup vent at the far end.
- Reading falls to zero at once: a breaker or GFCI tripped. Restart, start the backup unit, and recheck the circuit load.
- 1. Work area: poly walls and floor, held under negative pressure
- 2. Clean room, the entry from outside the containment
- 3. Ducha
- 4. Equipment room, next to the work area
- 5. Makeup air enters through the decon chambers, at the end opposite the machines
- 6. Air sweeps across the work area toward the machines, so clean air crosses the workers toward the HEPA units
- 7. Negative air machines at the far end from the decon entry
- 8. Flex duct carries the exhaust through the wall to outdoors; clamp and tape each joint so it seals
- 9. Manometer or pressure recorder reading the difference across the barrier; your project specification sets the target
- 10. Waste load-out, where bagged waste leaves the work area
Schematic, not to scale. Chamber sizes, layers and the pressure target come from your project specification.
Replacement HEPA filters and pre-filters by machine
Filters load in order: the pre-filter takes the bulk dust and often goes daily during heavy removal, the ring panel or pleated secondary goes when a fresh pre-filter no longer restores the reading, and the HEPA goes last, when the gauge, change lamp or alarm says so. Bag used filters inside the containment and handle them as asbestos waste under your project specification, using asbestos disposal bags.
INLINE's wood HEPA filters are all 11-1/2 in deep and rated 99.97 percent at 0.3 micron, in faces from 12 x 12 to 24 x 24 in. Ring panels come 24 to a case and primary pre-filters 50 to a case, both in 16 x 24 and 24 x 24 among other sizes.
| Machine | Stages listed | Replacement match |
|---|---|---|
| MachineAeroclean Mighty Mite 1800 | Stages listed24 x 16 pre-filter, 24 x 16 x 1 ring panel, 24 x 16 x 11-7/8 HEPA | Replacement match16 x 24 pre-filters and ring panels; the 16 x 24 wood HEPA is 3/8 in shallower |
| MachineNovatek Novair 2000 | Stages listed24 x 24 x 11.5 HEPA or nuisance dust filter, 1/2 in pad ring | Replacement match24 x 24 x 11-1/2 wood HEPA, 24 x 24 pre-filters |
| MachineAbatement Technologies 2000, Bulldog | Stages listed6 in deep 99.97 percent HEPA; accepts 12 in deep | Replacement matchFace size by quote |
| MachineDri-Eaz HEPA 700 | Stages listed2 in MERV 8 pre-filter, primary HEPA | Replacement matchDri-Eaz 125026 pre-filter, 125028 HEPA |
| MachinePhoenix Guardian R | Stages listed1 x 18 x 18 pleated, 2 x 18 x 18 HEPA | Replacement matchBy quote |
| MachineINLINE 2000 and 700 | Stages listedPolypad or coarse prefilter, pleated prefilter, 99.97 percent tested HEPA | Replacement matchBy quote |
Products mentioned on this page
Dri-EazDucto Dri-Eaz Layflat


Questions contractors ask
Does a 2,000 CFM negative air machine really move 2,000 CFM with duct on it?
Usually not once the HEPA loads and duct is attached. The label is clean-filter airflow; only the Novatek Novair 2000 listing says its 2,000 CFM is with filters in place. Plan each 2,000 CFM unit at about 1,400 CFM and let the manometer confirm the containment holds.
What size poly tubing fits a 12 inch exhaust collar?
Poly tubing 20 in wide flat fits a 12 in collar. A 20 in flat width opens to about 12.7 in round, so it slides over the collar on the Abatement Technologies 2000, Bulldog and Aeroclean machines and can be clamped or taped. INLINE sells 6 mil clear poly tubing 20 in by 500 ft.
How many negative air machines can I plug into one 15 amp circuit?
Plan to 12 A of continuous load on a 15 A circuit and divide by each unit's listed amps: 5 Phoenix Guardian R units at 2.4 A, 4 XPOWER X-2480A or Dri-Eaz HEPA 700 units, 3 ACSI FA700 units, or 1 Aeroclean Mighty Mite 1800 at 9.4 A. The Novatek Novair 2000 (15 A) and ACSI Force Air 2000EC (20 A listed) each need their own circuit.
Can a negative air machine pull too much on a small containment?
Yes. A large unit on a small room can suck the poly inward and pull tape loose. A unit rated at 2,000 CFM moves about 187 air changes an hour in a 640 cu ft bathroom. Use a 700 CFM class unit on low, a variable unit such as the OmniAire 2000V turned down, or open a filtered makeup vent at the end away from the machine.
What should the manometer read on an asbestos containment?
Many abatement specifications set a minimum of 0.02 in. of water column below the surrounding area, about 5 pascals; your project specification sets the exact figure and how it is recorded. A reading that climbs while the poly bows in means the room is over-negative; one that drifts down means filters are loading or a seam has opened.
Do I need a backup negative air machine on an asbestos job?
Plan for one whenever the job's requirements call for it, and many do. Size the standby to at least match the largest running unit, so a filter change or breaker trip does not drop the containment, and put it on a separate circuit from the units it backs up.
Which negative air machine fits through a standard doorway?
The narrowest large unit is the Aeroclean Mighty Mite 1800 at 18 in wide and 94 lb. The INLINE 2000, Aeroclean 2000 Econo and Novatek Novair 2000 are 26 in wide, and the ACSI Force Air 2000EC lists 37-1/8 x 26.5 x 32.5 in. Smaller stackable units weigh far less: the Dri-Eaz HEPA 700 is 42 lb, the Phoenix Guardian R 33 lb and the XPOWER X-2480A 23.6 lb.
Will a 24 x 24 x 11-1/2 wood HEPA filter fit my negative air machine?
It matches the Novatek Novair 2000, which lists a standard 24 x 24 x 11.5 in HEPA. It does not match the Aeroclean Mighty Mite 1800, which uses a 24 x 16 x 11-7/8 in HEPA, or the Abatement Technologies units, which take a 6 in or 12 in deep HEPA. For other machines, send the make and model through the quote form before you order.